VS

Install the circulator on the delivery pipe or on the return pipe. The arrow stamped on the pump body indicates the direction of flow.

Install an on-off valve on both the suction pipe and the delivery pipe.

ALWAYS fit the circulator with the motor shaft horizontal, avoiding dripping onto the motor and onto the terminal board.

Circolatore VS installazione

In case of thermal insulation, ensure that the condensate drainage holes in the motor casing are not closed or partially blocked.

Isolamento termico VS

Do not mix additives derived from hydrocarbons and aromatic products with the circulating water. Antifreeze max. 30% (VSA max. 60%). Provide an anti-scale system in plants having domestic circulators with water total hardness (TH) higher than 15°F.

VS Non mescolare acqua additivi

In the electrical connection to the power supply line, provide a two-pole switch with a contact opening distance of at least 3 mm. No motor overload protection is required. The instruction manual of the VS circulator (also available in our DNA software) provides all the indications to follow for the use of the product.

The circulator does not start

  1. Check the electric voltage
  2. Check the state of the capacitor
  3. Rotor blocked by deposits on the bushing

 

Noise in the system

  1. Flow rate too high
  2. Air in the system

 

Noise in the circulator

  1. Air in the circulator
  2. Suction pressure too low

 

The three-phase circulator does not reach the desired performances

  1. The circulator is turning in the opposite direction. Invert the electrical connection.

 

The circulator stops after having worked a short time

  1. Check that the shaft is turning freely. Remove any dirt and/or scale

 

The three-phase circulator stops after having worked a short time

  1. Check the electrical connections and the correct power supply of the three phases

 

The instruction manual of the VS circulator (also available in our DNA software) provides all the indications to follow for the use of the product.

On the product there is an arrow who show the direct of the rotation. If the rotation is in the wrong direction, invert two of the three electric connections.

VS circulator

The instruction manual of the VS circulator (also available in our DNA software) provides all the indications to follow for the use of the product.